21 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases.They are standardised at 11 % oxygen in waste gas except in case of incineration of mineral waste oil as defined in point 3 of Article 3 of Directive 2008/98/EC, when they are standardised at 3 % oxygen, and in the cases referred to in Point 2.7 of Part 6
26 The competent authority may authorise exemptions from the emission limit values set out in this point for waste incineration plants using fluidised bed technology, provided that the permit sets an emission limit value for carbon monoxide (CO) of not more than 100 mg/Nm3 as an hourly average value
39 For technical provisions regarding 'Monitoring of emissions' see Part 6 (Annex VI). For 'Formula to calculate the emission concentration at the standard percentage oxygen concentration' see Part 7 (Annex VI). For 'Assessment of compliance with emission limit values' see Part 8 (Annex VI) Directive 2010/75/EU
|